7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 63
mmmmm
Rake (Screen) Control
Setting the Common Parameters
Prerequisite: Substitute the details of your application in place of the sample values
provided. If you are bench testing the unit, set your test values to be the same as the
sample values.
Set Relay 1 (Operate Rake)
Set Relays 2 to 4 (Level Alarms)
Parameter Index Value Description
P001 G 4 Operation = Differential
P002 G 1 Material = liquid
P003 1,2 2 Max. Process Speed = medium
P004 1,2 102 Transducer = XPS-10
P005 G 1 Units = meters
P006 1
2
1.8
2.2
Empty
Empty
= 1.8m
= 2.2m
P007 1
2
1.4
1.4
Span
Span
= 1.4m
= 1.4m
Parameter Index Value Description
P110 1 3
Starts the rake when the difference between the
two levels rises above 0.4m and stop the rake
when the difference falls below 0.1m.
P111 1 50
P112 1 0.4
P113 1 0.1
P110 2 1 Description
P110 2 1
Sets Relay Two as a high level alarm for
Transducer One with an ON setpoint of 1.3m
and an OFF setpoint of 1.2m.
P111 2 1
P112 2 1.3
P113 2 1.2
P110 3 2
Sets Relay Three as a low level alarm for
Transducer Two with an ON setpoint of 0.2m
and an OFF setpoint of 0.4m.
P111 3 1
P112 3 0.2
P113 3 0.4
P110 4 3 Sets Relay Four as a rake failure alarm as it
uses the differential level point (3) with an
ON setpoint of 1.0m and an OFF setpoint of
0.9m.
P111 4 1
P112 4 1.0
P113 4 0.9