7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 187
mmmmm
Parameters
P791 Bus Error
Indicates if an error condition is occurring on the bus.
P792 Bus Error Count
A count that changes by increments of one each time a bus error (P752) is reported.
Echo Processing (P800 to P807)
P800 Near Blanking
The space near the transducer face which cannot be measured.
Use this feature if the surface is reported to be near the transducer face but is in fact
further away. Extend this value when changing transducer location, mounting, or aiming.
Please note that changing the Near Blanking cannot correct measurement problems.
Ensure that Span (P007) < Empty (P006) – Near Blanking (P800).
Primary Index Global
Values
0*No error
ý
Error code, refer to the SmartLinx module documentation for
explanation of the code
Related P790 Hardware Error P792 Bus Error Count
Primary Index Global
Values
Range: 0 to 9999
Preset: 0
Related P790 Hardware Error P791 Bus Error
Primary Index Global
Values
Range: 0.000 to 9999
Preset: 0.300m (Most transducers)
0.450m (XCT-8, XCT-12)
Related
P006 Empty
P007 Span
P833 TVT Start Min