Siemens HydroRanger 200 Instruction Manual Page 136

  • Download
  • Add to my manuals
  • Print
  • Page
    / 256
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 135
Page 122 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
Examples:
If the measured value is in feet, enter 0.3333 to display the number of yards
For simple linear, volume conversions set POO5 to 1 (meters) and then enter the
volume measurement per unit to get the correct conversion. For example, if the
reservoir contains 100 litres per vertical meter, use 100 to get the reading in litres.
P062 Offset Reading
Adds the specified value to the level reading, usually to reference the reading to sea level
or another datum level.
The operation of the device is not affected by the Offset Reading. This value is used for
display purposes only. All control measurements are still referenced to Empty.
Backup Level Override
Use this feature to override the ultrasonic reading by a discrete input such as a
contacting point device. The ultrasonic reading will be fixed at the programmed switch
level until the discrete input is released.
The ultrasonic device makes decisions based on the override values.
P064 Reading Override Enable
Sets the discrete input to act as the source for a level reading override.
Primary Index Level
Values
Range: -999 to 9999
Preset: 0.000
Related P920 Reading Measurement
Primary Index Transducer
Values
0 * OFF: No override.
1-2 ON: Number = discrete input of override signal
Related
P065 Reading Override Value
P270 Discrete Input Function
Notes:
This method does not calculate volume. It must not be used in place of the volume
parameters if any volume dependent features (such as pump efficiency) are used.
To calculate true volumes see Volume (P050 to P055).
Avoid entering a value that, when multiplied by the maximum current Reading,
exceeds the display capabilities. If value exceeds four digits, EEEE is shown.