Page 138 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
P173 Flush Duration
The length of time for each flush cycle that the flush control is active.
mA Output (P200 to P219)
P200 mA Output Range
Determines the mA output range.
If either 1 or 2 is selected, the mA output is directly proportional to the mA Function. If
either 3 or 4 is selected, then the output is inversely proportional.
Primary Index Global
Values
Range: 0.000 to 9999 s
Preset: 0.000
Related P111 = 64, Flush Valve
Primary Index mA output
Values
0off
1 0 to 20 mA
2* 4 to 20 mA
3 20 to 0 mA
4 20 to 4 mA
Related P911 mA Output Value