7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 205
mmmmm
Parameters
P910 Toggle Relays
Used to energize and de-energize relays directly.
Enter the relay number and then toggle between
energized
and
de-energized
, as
required. Enter 0 to toggle all relays at once.
Applies only to relays with P119 = 0 (algorithm control). Use this parameter to confirm that
relay contacts are opening and closing.
This feature is helpful when P119 does not give expected results even though
programming was verified.
P911 mA Output Value
Access this parameter to display the current value of the mA output.
Additionally, this feature may be used to enter a value. The mA output immediately
assumes the value entered regardless of any restrictions programmed.
P912 Transducer Temperature
Use this feature to display the temperature in °C (as monitored by the connected
transducer).
Err is displayed if the transducer is not equipped with an internal temperature sensor.
Primary Index Global
Values 0 to 6
Related P119 mA Relay Logic Test
Primary Index mA output
Values Range: 0.00 to 25.00
Related
P200 mA Output Range
P201 mA Output Function
Primary Index Transducer
Values Range: -50 to 150