7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 203
mmmmm
Parameters
Test (P900 to P913)
Test Parameters are intended for use by Siemens Milltronics Service personnel.
P900 Software Revision Number
View the EPROM Rev. #.
P901 Memory
Press ENTER to activate the HydroRanger 200 memory test.
P902 Watchdog
Press ENTER to put the CPU into an infinite loop to test the watchdog timer.
On successful completion (10 seconds) the RUN mode is entered and the HydroRanger
200 is reset. Programming is kept and the unit responds as if there had been a power
failure.
P903 Display
Press ENTER to activate the display test.
All LCD segments and symbols are temporarily displayed.
Primary Index Global
Values Range: 00.00 to 99.99 (view only)
Primary Index Global
Values
Display: view only
PASS (memory test successful)
F1 RAM
F3 FLASH data
F4 FLASH code