Error Handling
Communication Troubleshooting
Generally
1. Check the following:
There is power at the unit
The LCD is showing the relevant data
The device can be programmed using the hand programmer
2. Check the wiring pin outs and verify that the connection is correct.
3. Verify that values in the set-up parameters (P770 to P779) match the settings in the
computer used to communicate with the unit.
4. Check that the port on the computer is correct. Sometimes trying a different Modbus
driver will solve the problem. An easy stand-alone driver called ModScan32 is
available from Win-Tech at www.win-tech.com. This driver is helpful for testing
communications.
Specifically
1. The HydroRanger 200 is set to communicate via a modem but no communication is
returning to the master.
Check that the parameters are set up correctly and that the correct port is
configured
Verify the wiring diagram. Note that there is a difference between wiring directly
to a computer and wiring to a modem. Verify that the modem is set up correctly.
Milltronics has a series of Application Guides that may help. Please contact your
local Siemens Milltronics representative for more information on Application
Guides.
2. A HydroRanger 200 parameter is set via remote communications, but the parameter
remains unchanged.
Some parameters can only be changed when the Milltronics device is not
scanning. Try putting the Milltronics device in program mode, using the
operating mode function.
Try setting the parameter from the keypad. If it can not be set using the keypad,
check the lock parameter and set it to 1954.