Parameters
Rate (P700 to P708)
These parameters determine how material level changes are reported.
P700 Max Fill Rate
Adjusts the HydroRanger 200 response to increases in the actual material level (or
advance to a higher Failsafe Material Level, P071).
Enter a value slightly greater than the maximum vessel filling rate. This value, in Units
(P005) or % of Span (P007) per minute, is automatically altered when Maximum Process
Speed (P003) is altered.
P701 Max Empty Rate
Adjusts the HydroRanger 200 response to decreases in the actual material level (or
advance to a lower Failsafe Material Level, P071).
Enter a value slightly greater than the maximum vessel emptying rate. This value, in Units
(P005) or % of Span (P007) per minute, is automatically altered when Maximum Process
Speed (P003) is altered.
Primary Index Global
Values Range: 0.000 to 9999
Altered by P003 Maximum Process Speed
Related
•P005 Units
•P007 Span
P071 Failsafe Material
Level
P003 Value Meters/Minute
10.1
2 1
310
Primary Index Global
Values Range: 0.000 to 9999
Altered by P003 Maximum Process Speed
Related
P005 Units
P007 Span
P071 Failsafe Material
Level
P003 Value Meters / Minute
10.1
2 1
310