7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 91
mmmmm
Modbus Register Types
Modbus Register Map
Features affecting
volume
,
mA input
, and
Average or Difference
readings apply to the
HydroRanger 200 only. They are clearly marked.
The memory map of the HydroRanger 200 occupies the Modbus holding registers
(R40,001 and up). This map is used when the protocol is Modbus RTU slave or Modbus
ASCII slave.
Register Map for Most Common Data
Legend
Type The type of data held in the group of registers.
Start The first register to hold the referenced data.
Data Type The possible values of the data in the register. See
Data Types
on page
101 for more information.
Description The type of data held in the individual registers.
#R The number of registers used for the referenced data.
Read/Write Indicates whether the register is readable, writeable or both.
Type Description Start
#R
1
1.
Maximum registers shown; fewer may be used depending on options installed.
Data Type
Read/
Write
Word Order 40,062 0/1 R/W
Map ID
Register Map Type 40,063 1 0/1 = P782
R/W
ID
Milltronics Product
Code
40,064 1 4 = Model 200
6 = Model 100
R
Single Parameter Access (SPA)
R40,090 7
see Comms Appendix A on page 108
Point
Data
Reading (3)
2
2.
Available as reading 1, reading 2, and Average or Difference. Point 2 and 3 are only
available if P001 = Average or Difference.
41,010 2 -20,000 to 20,000
R
Volume (2) 41,020 2 -20,000 to 20,000