7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 125
mmmmm
Parameters
Selecting HI, LO, or HOLd
1. Press FUNCTION to display the Auxiliary Function symbol.
2. Press ARROWS
to scroll to the desired option.
3. Press ENTER to set the value.
Entering a Measurement
To enter a specific Failsafe Material Level within -50 to 150% of Span (P007), in Units
(P005).
Relay reaction
The way in which relay programming reacts to the failsafe level depends on P129 Relay
Failsafe (page 132). By default:
Alarm relays have P129 = OFF and so react to the Failsafe Material Level.
Control relays have P129 = dE and so de-energize the relay when the unit enters
Failsafe mode regardless of the Failsafe Material Level.
P072 Failsafe Level Advance
Sets the speed the HydroRanger 200 advances to and returns from the Failsafe Material
Level.
Primary Index Level Point
Values
1 * Restricted
Advances to/from Failsafe Material Level as set by
P003, P700 and P701.
2 Immediate Failsafe Material Level assumed right away
3Fast Back
Failsafe Level Advance is restricted, return is
immediate
Related
P003 Maximum Process Speed
P070 Failsafe Timer
P071 Failsafe Material Level
P700 Max Fill rate
P701 Max Empty rate