Page view 81
Page 68 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmm
m
Open Channel Monitoring
Setting Totalized Volume
To display the totalized volume on the LCD use the following parameters:
Applications Supported by HydroRanger 200
BS-3680 / ISO 1438/1 Thin plate V notch weir
Parameter Index Value Description
P737 G 2 Show the eight digit totalizer in the primary
display
Parameter Index Value
P600 G 7–ISO 1438/1 V Notch Weir
P602 1 Notch angle
(view only) 2 Discharge coefficient (Ce)
P603 G Maximum Head (preset to P007)
P801 G Range Extension
P608 G Flowrate Units
P801
P006
Transducer
4 to 5 x h
max
(h
max
= P007)
Plan View
Side View
Front View
P602
notch angle
P603
P007