7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 51
mmmmm
Pump Control
Pump Control
Setting a Pump Down Group
Example: Sewage Wet Well
Setting a group of three pumps to pump down a wet well.
Set the Common Parameters
Prerequisite: Substitute the details of your application in place of the sample values
provided. If you are bench testing the unit, set your test values to be the same as the
sample values.
Parameter Index Value Description
P001 G 1 Operation = level
P002 G 1 Material = liquid
P003 G 2 Maximum Process Speed = medium
P004 G 102 Transducer = XPS-10
P005 G 1 Units = meters
P006 G 1.8 Empty = 1.8m
P007 G 1.4 Span = 1.4m
HydroRanger
200
P006
P007
Inflow
Outflow