Page 114 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
For these operations any of three level points (transducer 1, transducer 2, or the
calculated point) can be used to trigger relays (see P110 on page 127).
The points must be globally set to either 4 or 5 (as required). Point 3 becomes the
calculated value as shown above. See
Rake Control
example on page 62.
P002 Material
Specifies material type.
P003 Maximum Process Speed
Determines level change reaction.
Use a setting just fast enough to keep up with your process. Slower settings provide
higher accuracy. Faster settings allow for more level fluctuations.
Primary Index Global
Values
1 * Liquid or horizontal solid surface
2 Solid or angled surface
Alters P830 TVT Type
Primary Index Transducer
Values
1 Slow (0.1 m/min)
2 * Medium (1 m/min)
3 Fast (10 m/min)
Alters
P070 Failsafe Timer
P700 Max Fill Rate
P701 Max Empty Rate
P702 Filling Indicator
P703 Emptying Indicator
P704 Rate Filter
P710 Fuzz Filter
P713 Echo Lock Window
P727 Scan Delay
P841 Long Shot Number
Related
Failsafe (P070 to P072)
•P121 Pump by Rate
Rate (P700 to P708)
Measurement Verification (P710 to P713)
Transducer Scanning (P726 to P729)
P905 Transmit Pulse