Page 140 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
P203 mA Output Value / Transducer
Displays current mA output value for the Point Number.
This displays as an Auxiliary Reading when key is pressed in the RUN mode and
does not include adjustments made using Trim features (P214 / P215).
Independent mA Setpoints (P210 and P211)
Use these features to reference the minimum and/or maximum mA output to any point in
the measurement range.
Primary Index Level
Values Range: 0.000 to 22.00 (view only)
P201—mA Function
Settings
Action
Level, Space, or Distance
Enter the material level in Units (P005) or percent of
Span (P007) as referenced to Empty (P006).
Volume
Enter the volume in Max Volume (P051) units or as a per-
cent of Max Volume.
Flow
Enter the flowrate in OCM Max Flow (P604) units or as a
percent of OCM Max Flow.
Head
Enter the head in level units (P005) or percent of Max
Head (P603).
Volume Rate
Enter the volume rate in volume/min. Ensure the % sym-
bol is displayed before attempting to enter a % value.
mA input or
Communications Input
Not Applicable
Note: This parameter is applicable only if any mA output has the transducer Point
Number as its input source (see P201 and P202).