7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 181
mmmmm
Parameters
Selecting the Auxiliary Reading operation
1. Press READING to display the Auxiliary Function symbol.
2. Press ARROWS to access the OFF or HOLd option desired.
3. Press ENTER
If necessary, enter the Parameter Number to default in the Auxiliary Reading display. That
value will show in the auxiliary reading area by default. Other values are available but will
reset to the parameter defined here.
P731 Auxiliary Reading Key
Enter the Parameter Number whose value is to be displayed in the Auxiliary Reading field
is pressed in the RUN mode. See the
Hand Programmer
section on page 22 for RUN
mode auxiliary readings.
P732 Display Delay
Adjusts the Point Number display scroll speed.
Use this feature to adjust the delay before the display advances to the next Point Number.
Display scrolling is independent from transducer scanning.
Primary Index Global
Values
Range: 000 to 999
Preset: Material Reading, P921
Primary Index Global
Values
Range: 0.5 to 10
Preset: 1.5 seconds
Related
•P001 Operation
P737 Primary Reading
P