7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 129
mmmmm
Parameters
P113 Relay OFF Setpoint
Sets the process point at which the relay returns to its NORMAL state.
For most applications, the relay is reset at this point. For IN-BOUNDS and OUT-OF-
BOUNDS alarms, it is the low point in the specified range. This parameter is set to Span
(P007), even when another reading, such as volume, is shown on the LCD.
P115 Relay Interval Setpoint
The length of time in hours between flow samplers (if P111 = 41).
P116 Dead Band
The distance above and below the bound alarm setpoints
For IN-BOUNDS and OUT-OF-BOUNDS Relay Functions (P111 = 2 and 3 respectively), a
dead band prevents relay chatter due to material level fluctuations at both the upper and
lower setpoints.
Primary Index Relay
Values
Range: -999 TO 9999
Preset: ----
Altered by •P007 Span
Related
P100 Preset Applications
P111 Relay Control Function
P112 Relay ON Setpoint
Primary Index Relay
Values
Range: -999 TO 9999
Preset: 0.000
Altered by P100 Preset Applications
Related P111 Relay Control Function
Primary Index Relay
Values
Range: 0.000 to 9999
Preset: 2% of span
Related
P111 Relay Control Function
P112 Relay ON Setpoint
P113 Relay OFF Setpoint
Enter the dead band in either percent of
span or units of measure (P005). The dead
band value is applied both above and
below the upper and lower bound set-
points as shown in the figure.
Actual ON or OFF setpoint
Actual OFF or ON setpoint
P116
P116
Setpoint set in P112 or P113