7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 45
mmmmm
Volume
Characterization Chart
If you cannot use a pre-defined tank, then use one of the universal tank shapes and
program the characterization curve.
1. Plot a volume to height chart. Usually a tank supplier will provide this chart.
However, if you have a custom-built wet well then you will need access to complete
drawings of the well or accurate measurements.
2. Enter the curve values from this chart into P054 and P055.
3. Ensure extra points are added around sharp transitions in the wet well volume (e.g:
as steps in the well wall).
Example Chart
See table below for index values and descriptions
Note: The end points in the curve are 0,0 (fixed) and the point defined by P007–Span
and P051–Maximum Volume.
FLOW
LEVEL (P054)
0,0
VOLUME (P055)
MAX VOLUME
P051