7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 157
mmmmm
Parameters
P342 Start Ups
The number of times power has been applied since the Date Of Manufacture.
Open Channel Monitoring (P600 to P621)
If the HydroRanger 200 is used to monitor open channel flow, alter the following
parameters as required and run a calibration as described in P621.
The HydroRanger 200 measures head as referenced to Empty (P006) or OCM Zero Offset
(P605), when Operation is set for OCM (P001 = 6). Flowrate, based on head (at the point of
measure specified by the Primary Measuring Device fabricator) is also calculated and
displayed on the LCD.
Some Primary Measuring Devices require a longer Range Extension (P801) to avoid
entering the LOE failure state if the water level falls below the zero point of the Primary
Measuring Device. See
P801 Range Extension
on page 188 for more information.
P600 Primary Measuring Device
The type of primary measuring device (PMD) used.
Primary Index Global
Values Range: 1 to 9999 (view only)
Related
• P340 Date of Manufacture
• P342 Run Time
Primary Index Global
Values
0 * off (no calculation)
1 Exponential (see P601)
2 Palmer-Bowlus Flume (see P602)
3 H-Flume (see P602)
4 Universal Linear Flow Calculation (see P610, P611)
5 Universal Curved Flow Calculation (see P610, P611)
6 BS-3680/ISO 4359 Rectangular Flume (see P602)
7 BS-3680/ISO 1438/1 Thin Plate V-Notch Weir (see P602)
Note: See
Open Channel Monitoring
(OCM) on page 66 for application examples
involving common weirs and flumes.