Page 90 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1
mmmmm
Communications Installation
P778 Modem Available
Sets the HydroRanger 200 to use an external modem.
P779 Modem Inactivity Timeout
Sets the time that the unit will keep the modem connected with no activity.
To use this parameter, ensure that P778 (Modem Available) =1. Ensure that the value is
low enough to avoid unnecessary delays when an unexpected disconnect occurs but
long enough to avoid timeout while you are still legitimately connected. This parameter
value is ignored by the Modbus Master Drivers as they automatically disconnect when
done communicating.
Hanging Up
If the line is idle and the P779 Modem Inactivity Timeout expires, then the modem is
directed to hang up the line. Ensure that P779 is set longer than the standard polling time
of the connected master device. Set P779 to 0 to disable the inactivity timer.
P782 Parameter Index Location
Determines where index information is stored for the parameter access area for the
Modbus register map.
For more on Parameter Index Location, see
Parameter Access
on page 95.
Primary Index
Communications Port
Values
0 * No modem connected
1 Answer only
Primary Index
Communications Port
Values
Range: 0-9999 seconds
0*No timeout
Primary Index
Global
Values
0 * Global
1 Parameter-Specific