Page 34 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Relays
3
Relays
Relays are the primary controls of external devices
such as pumps or alarms.
The HydroRanger 200 comes with extensive control
and alarm functions.
General Introduction
Six onboard multi-purpose relays are provided on the HydroRanger 200. Each relay may
be independently assigned to one function with a corresponding status icon on the LCD.
The relay functions fall under three modes of operation:
Relay Function
Alarm
Level
In high alarm, the function goes on when the level rises to the ON setpoint and goes off
when the level lowers to the OFF setpoint. In low alarm, the function goes on when the
level lowers to the ON setpoint and goes off when the level rises to the OFF setpoint.
In Bounds
The relay will be in alarm if the level is inside the zone between the setpoints.
Out of Bounds
The relay will be in alarm if the level is outside the zone between the setpoints.
Rate of Change
In filling alarm, the function goes on when the rate of filling increases to the ON setpoint
and goes off when the rate of filling drops to the OFF setpoint. In emptying alarm, the
function goes on when the rate of emptying increases to the ON setpoint and goes OFF
when the rate of emptying drops to the OFF setpoint. For emptying alarm, the setpoints
must be entered as negative values.
Mode Function
alarm alarm ON = LCD Icon ON = relay coil de-energized
pump pump ON = LCD Icon ON = relay coil energized
miscellaneous contact closed = LCD Icon ON = relay coil energized
Relay Number
Ring indicates
relay is configured
Dot indicates relay
is energized/de-
energized