Page 134 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
P131 Pump Run-On Duration
Sets the number of seconds that the pump runs on.
Your pump capacity determines the amount of material that can be removed. Choose a
value long enough to clean out the vessel bottom, yet short enough not to run the pump
dry. Also be sure that this value does not overlap with P130 (Interval). The timing should
look something like this:
P132 Pump Start Delay
Sets the minimum delay (in seconds) between pump starts.
Use this feature to reduce a power surge from all pumps starting at the same time. This
delay determines when the next pump is permitted to start.
Primary Index Global
Values
Range: 0.0 to 9999
Preset: 0.000
Related • Advanced Pump Control Modifiers (P130 to P136)
Primary Index Global
Values
Range: 0.0 to 9999
Preset: 10 seconds
Value is divided by 10 in simulation mode.
Related
• Advanced Pump Control Modifiers (P130 to P136)
• P121 Pump by Rate
P131
P132
P130 (Pump Run-On)