7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 99
mmmmm
Modbus Register Types
Global Index Method (P782 = 0)
Only the final digit of the format word determines the decimal offset (below).
Parameter-Specific Index Method (P782 = 1)
All three decimal fields are used to determine the parameter value’s primary index,
secondary index, and decimal offset.
Format Registers
Each format register is made up of three decimal fields:
decimal offset
secondary index
primary index
The primary and secondary indices correspond to those that are used by the parameter.
The decimal offset indicates how the remote system must interpret the integer value that
is stored in the parameter access register. The following table shows how different
parameter values can be shown based on a register value (integer) of 1234.
Decimal Offset Example
00 1,234
1 –1 12,340
2 –2 123,400
3 –3 1,234,000
4 –4 12,340,000
5 –5 123,400,000
6 +1 123.4
7 +2 12.34
8+3 1.234
9 Percent 12.34%
primary index (00-64)
secondary index (00-99)
decimal offset (0-9)