7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 7
mmmmm
Installation
Installation
Mounting
Mounting Locations
Recommended
Ambient temperature is always within -20 to 50°C (-5 to 122°F)
HydroRanger 200 display window is at shoulder level, unless most interaction is
through a SCADA system
Easy access for hand programmer is provided
Cable length requirements are minimal
Mounting surface is free from vibration
A place for a laptop computer is provided for on-site Dolphin Plus configuration
Avoid
Exposure to direct sunlight. (Provide a sun shield to avoid direct sunlight.)
Proximity to high voltage/current runs, contacts, SCR or variable frequency motor
speed controllers
Notes:
Installation must only be performed by qualified personnel, and in accordance
with local governing regulations.
This product is susceptible to electrostatic shock. Follow proper grounding
procedures.
All field wiring must have insulation suitable for at least 250 V.
Hazardous voltage present on transducer terminals during operation.
DC terminals shall be supplied from an SELV source in accordance with IEC
1010-1 Annex H.
The non-metallic enclosure does not provide grounding between conduit
connections. Use grounding type bushings and jumpers.