Page 126 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
Relays (P100 to P119)
The HydroRanger 200 has six relays (or digital outputs) used to control devices and
alarms. While the number of devices is limited by the relays, all control functions are
accessible through software and each parameter is indexed to the three or six relays.
See the
Relay
section on page 34.
Preset Applications (P100)
The HydroRanger 200 makes standard applications easier to program by providing an
extensive list of presets.
Control Functions (P111)
Each relay can be configured independently to take advantage of the HydroRanger 200’s
advanced features and flexibility. Start with a preset application and then change the
required parameters to make the task more efficient.
Setpoints (P112, P113)
Each relay is triggered by one or more setpoints. The setpoints can be based on absolute
level (P112, P113) or rate of change (P702, P703). Each control function specifies which
setpoints are required.
P100 Preset Applications
Six preset applications to configure or bench test the unit.
Select an application that is similar to yours and change the parameters required. If none
suit, then refer to P111 Relay Control Function on page 127.
Primary Index Global
Values
0 * OFF
1Wet Well 1
2Wet Well 2
3 Reservoir 1
4 Reservoir 2
5Screen
6Alarms
Alters
P110 Level Source
P111 Relay Control Function
P112 Relay On Setpoint
P113 Relay OFF Setpoint
•P121 Pump by Rate
Related •P001 Operation
Note: Programming the relays independently is the most common method used.