7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 93
mmmmm
Modbus Register Types
Product ID (R40,064)
Identifying Milltronics device type:
Point Data (R41,010 – R41,031)
Measurement point data contain the current instrument readings. These are the values
shown for the reading measurement for each measurement point. The reading is based
on the setting for P001 (operation). P001 can be set to level, distance, OCM flow, or
volume. See HydroRanger 200
Parameter Reference
section on page 113 for details.
The measurement registers are 41,010 to 41,012. The HydroRanger 200 uses 41,010 when
configured with a single transducer and 41,010 to 41,012 when configured with two
transducers (P111=4 or 5 only). Two transducers can create three readings because they
can generate an average or differential reading (R41,012) as well as the two level
readings (R41,010 and R41,011).
Available Registers:
The reading is expressed as a percentage of full scale, multiplied by 100:
Input/Output (R41,070 – R41,143)
The HydroRanger 200 has discrete inputs, mA inputs, mA outputs and relay outputs.
Details for each I/O type below..
Device Type Value
HydroRanger 200 4
Data Registers Parameter
Reading 41,010 to 41,012 P920
Volume 41,020, 41,021 P924
Temperature 41,030 and 41,031 P912
Reading Value
00.00%
5000 50.00%
7564 75.64%
20,000 200.00%