Alarms
In Bounds / Out of Bounds Range
Use the bounded range alarms to detect when the level is inside or outside of the range.
By using a bounded range alarm, you can effectively put two level alarms (high and low)
on one relay.
Setting an Out of Bounds Alarm
Results:
Trips alarm above 1.35m and below 0.25m
Resets alarm below 1.25m and above 0.35m
Setting an In Bounds Alarm
Results:
Trips alarm below 1.25m and above 0.35m
Resets alarm above 1.35m and below 0.25m
Cable Fault
Activates an alarm if transducer cable circuit enters a shorted or opened state.
Temperature
Use the temperature alarm to activate an alarm when the temperature reaches the ON
setpoint (P112). This alarm uses the same setpoint parameters as the level alarms (P112
and P113).
Parameter Index Value
P111 5 3
P112 5 1.3
P113 5 0.3
P116 5 0.05
Parameter Index Value
P111 5 2
P112 5 1.3
P113 5 0.3
P116 5 0.05
Parameter Index Value Description
P111 5 7 Alarm on transducer cable fault
P110 5 1 Alarm on Transducer One