Page 162 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
P607 Flowrate Decimal
The maximum number of decimal places to be displayed.
In RUN mode, the number of decimal places displayed is automatically adjusted (if
necessary) to prevent the number of Flowrate digits from exceeding display capabilities.
P608 Flowrate Units
The volume units used to display total flow.
Primary Index Global
Values
0 no digits after the decimal point
1 1 digit after the decimal point
2 2 digits after the decimal point
3 3 digits after the decimal point
Altered By P060 Decimal Position (sets max. number)
Primary Index Global
Values
Ratiometric (P600=all)
0 * Ratiometric calculation (units defined by P604)
Absolute (P600=6,7 only)
1 litres / second
2cubic metres / hour
3cubic metres / day
4 cubic feet / second
5 gallons / minute – Imperial
6 million gallons / day – Imperial
Values
7 gallons / minute – U.S.
8 million gallons / day – U.S.
Alters P606 Time Units
Altered By P600 Primary Measuring Device
Related P608 Flowrate Units