Page 142 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
P213 mA Output Max Limit
Sets the maximum mA output value (in mA) to be produced.
mA Output Trim (P214 to P215)
This does not affect the P203 value shown, and is used when recalibration of an external
device is impractical.
P214 4 mA Output Trim
Calibrates the 4 mA output.
Adjust this value so the device indicates 4.000 mA when P214 is accessed.
P215 20 mA Output Trim
Calibrates the 20 mA output.
Adjust this value so the device indicates 20.00 mA when P215 is accessed.
Primary Index mA output
Values
Range: 0.000 to 22.00
Preset: 20.2 mA
Related P200 mA Output Range / P212 mA Output Min LImit
Primary Index mA output
Values Range: 0 to 9999
Related P215 20 mA Output Trim
Primary Index mA output
Values Range: 0 to 16000
Related P214 4mA Output Trim