Page view 191
Page 178 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
If a material agitator (mixer) is used in the vessel monitored, set Echo Lock for maximum
verification or material agitator to avoid agitator blade detection. Ensure the agitator is
always on while the HydroRanger 200 is monitoring the vessel to avoid stationary blade
detection.
When set for max verification or material agitator, a new measurement outside of the
Echo Lock Window (P713) must meet the sampling criterion (P712).
For total lock, Echo Lock Window (P713) is preset to zero 0. The HydroRanger 200
continuously searches for the best echo according to the algorithm chosen (P820). If the
selected echo is within the window, the window is then centered about the echo. If not,
the window widens with each successive shot until the selected echo is within the
window. The window then returns to its normal width.
When Echo Lock is off, the HydroRanger 200 responds immediately to a new
measurement as restricted by the Max Fill / Empty Rate (P700 / P701); however,
measurement reliability is affected.
P712 Echo Lock Sampling
The sampling criterion sets the number of consecutive echoes appearing above or below
the echo currently locked onto, that must occur before the measurements are validated
as the new reading (for Echo Lock P711 values: 1 or 2).
Example:
Setting
P711 = 2, material agitator
P712 = 5:2
Result
a new reading will not be validated unless five consecutive measurements higher or
two consecutive measurements lower than the current reading occur
Resetting P711 returns P712 to the respective preset values
Primary Index Global
Values
Range: 1:1 to 99:99
Format: x:y
x = the number of above echoes
y = the number of below echoes
Related P711 Echo Lock
P711 value P712 preset value
1, max verification 5:5
2, material agitator 5:2