Parameters
P850 Short Shot Bias
Use this feature to slant the echo evaluation in favour of the short shot echo when both
short and long shots are evaluated (see P803 Shot Mode) .
P851 Short Shot Floor
Enter the minimum echo strength (in dB above 1 uV) derived from a short shot to be
considered for evaluation.
P852 Short Shot Range
Enter the maximum distance in Units (P005) to be measured using short shot echoes.
This feature is automatically altered when Transducer (P004) is altered.
Primary Index Global
Values
Range: 0 to 100
Preset: 20
Related
• P803 Shot / Pulse Mode
• P840 Short Shot Number
• P842 Short Shot
Frequency
• P844 Short Shot Width
• P851 Short Shot Floor
• P852 Short Shot Range
Primary Index Global
Values
Range: 30 to 100
Preset: 50
Related
• P840 Short Shot Number
• P842 Short Shot
Frequency
• P844 Short Shot Width
• P850 Short Shot Bias
• P852 Short Shot Range
Primary Index Global
Values Range: 0.000 to 9999
Altered By •P004 Transducer
Related
• P840 Short Shot Number
• P842 Short Shot
Frequency
• P844 Short Shot Width
• P850 Short Shot Bias
• P851 Short Shot Floor