7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 123
mmmmm
Parameters
P065 Reading Override Value
This value is substituted for the current reading when the selected discrete input is
enabled and activated.
Please note the following:
enter value in current units (as selected in P005)
valid for level, space, and distance
volume is calculated based on the Backup level
Example:
Transducer One is configured for a level measurement. Digital Input 2 is connected to a Hi
Level Backup switch located a level of 4.3m.
When the level rises to 4.3m, and the switch is activated, the reading is forced to 4.3m.
The reading stays at 4.3m until the switch is de-activated.
P066 Override Time Delay
Defines the time used to calm (debounce) the override condition input. Set in seconds.
Primary Index Transducer
Values Range: 0.0 to 9999
Alters Current reading
Related
•P001 Operation
•P005 Units
•P006 Empty
•P007 Span
P064 Override Enable
Parameter Index Value
P064
1
2
P065
1
4.3
Primary Index Transducer
Values
Range: 0.0 to 9999
Preset: 5.0
Related
P064 Override Enable
P065 Reading Override Value
P270 Discrete Input Function
Note: Activation of the Level Override is subject to the measurement cycle. This can
add up to four seconds to the overall response time depending on operating conditions
and programming.