7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 117
mmmmm
Parameters
Always prevent the monitored surface from approaching within 0.33m (1 ft) of the
transducer face as this is the minimum blanking for most Siemens Milltronics transducers
(some require more blanking – see your transducer manual).
Many other parameters are set as a percentage of span (even if they are entered in
units). The values of these other parameters may change if the span is altered after
installation and the other parameters are measured using a level determined upward
from the Empty level toward the transducer face.
Volumes are based on span. Set for the maximum volume point if volume calculations are
needed.
Volume (P050 to P055)
Please note that the volume parameters apply only to the HydroRanger 200.
Use these parameters to configure the HydroRanger 200 to show readings based on
vessel or wet well volume (rather than level).
P050 Tank Shape
Enter the Tank Shape value matching the monitored vessel or wet well.
When Operation is LEVEL (P001 = 1), liquid (material) volume is calculated.
Alternatively, when Operation is SPACE (P001 = 2), remaining vessel capacity is
calculated. In RUN mode, readings are displayed in percent of maximum volume. To
convert readings to volumetric units, see Maximum Volume (P051
Primary Index Global
Values
# Shape Description
0*
volume calculation not required
(preset)
1 Flat Level Bottom
2 Cone/Pyramid Bottom
3 Parabola Bottom