Siemens HydroRanger 200 Instruction Manual

Browse online or download Instruction Manual for Measuring, testing & control Siemens HydroRanger 200. Siemens HydroRanger 200 Instruction manual User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 256
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews

Summary of Contents

Page 1 - HYDRORANGER 200

HYDRORANGER 200Instruction Manual October 2002HYDRORANGER 200

Page 2 - Disclaimer of Liability

viiimmmmmTable of ContentsP622 Inflow / Discharge Adjust...

Page 3

Page 86 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmCommunications InstallationCommunications InstallationWiring Guidelines• the RJ-11 cable

Page 4

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 87mmmmmCommunications InstallationPort 1: RS-232 RJ-11 Jack To connect the unit to a PC using a

Page 5

Page 88 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmCommunications InstallationTo connect the unit to a modem using an RS-485 port:Configuri

Page 6

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 89mmmmmCommunications InstallationP772 Baud RateThe communication rate with the master device.T

Page 7

Page 90 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmCommunications InstallationP778 Modem AvailableSets the HydroRanger 200 to use an extern

Page 8

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 91mmmmmModbus Register TypesModbus Register MapFeatures affecting volume, mA input, and Average

Page 9

Page 92 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmModbus Register TypesThe HydroRanger 200 was designed to make it easy for master devices

Page 10 - Table of Contents

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 93mmmmmModbus Register TypesProduct ID (R40,064)Identifying Milltronics device type:Point Data

Page 11

Page 94 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmModbus Register TypesDiscrete Inputs (R41,070) This table shows the current status of th

Page 12

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 95mmmmmModbus Register TypesPump OFF Setpoint (R41,430 – R41,435) The OFF setpoint level (P113)

Page 13

ixmmmmmTable of ContentsP773 Parity ...

Page 14

Page 96 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmModbus Register TypesUsually, the parameters are all read / write.Each parameter registe

Page 15

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 97mmmmmModbus Register TypesGlobal Index Method (P782 = 0)Global format method sets index value

Page 16 - Configuration Examples

Page 98 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmModbus Register Types2. Read the value from the appropriate parameter register (the exam

Page 17 - Specifications

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 99mmmmmModbus Register TypesGlobal Index Method (P782 = 0)Only the final digit of the format wo

Page 18

Page 100 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmModbus Register TypesExamples of using the format word for both the index values and th

Page 19

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 101mmmmmData TypesData TypesThe HydroRanger 200 parameters do not always use integers to hold v

Page 20 - Transducers

Page 102 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmData TypesFor example, if R41,442 is read as a UINT32, the 32 bits would look like this

Page 21 - Installation

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 103mmmmmData TypesText MessagesIf a Milltronics device parameter returns a text message, that m

Page 22 - Mounting Instructions

Page 104 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmData TypesRelay Function Codes (P111 Only) If a Milltronics device parameter returns a

Page 23 - HydroRanger 200 Board

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 105mmmmmError HandlingError HandlingModbus ResponsesWhen polled by a Modbus Master, a slave dev

Page 24 - Optional Equipment

xmmmmmTable of ContentsP901 Memory ...

Page 25 - Please note:

Page 106 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmError Handling• If P000 is activated, then the value will be ignored and no error respo

Page 26 - Terminal Board

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 107mmmmmError HandlingCommunication TroubleshootingGenerally1. Check the following:• There is p

Page 27

Page 108 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmCommunication Appendix ACommunication Appendix A: Single Parameter Access (SPA)This App

Page 28 - Temperature Sensor

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 109mmmmmCommunication Appendix AWriting ParametersTo set parameters through Modbus do the follo

Page 29 - Level System Synchronization

Page 110 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmCommunication Appendix AError CodesThe error codes returned in the format area are 8-bi

Page 30 - Digital Communications

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 111mmmmmParametersParameter ReferenceThe HydroRanger 200 is configured through its parameters,

Page 31 - Operating the HydroRanger 200

Page 112 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersNotes

Page 32 - Readings in RUN Mode

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 113mmmmmParametersP000 LockSecures the HydroRanger 200 from changes. Access this parameter dire

Page 33 - Controlling the Display

Page 114 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersFor these operations any of three level points (transducer 1, transducer 2, o

Page 34 - Auxiliary Reading

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 115mmmmmParametersP004 TransducerSpecifies the Siemens Milltronics transducer connected to the

Page 35 - PROGRAM Mode

ximmmmmTable of ContentsObstructions in the Sound Beam ... 223

Page 36 - Starting PROGRAM Mode

Page 116 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP006 EmptyEnter distance in units (P005) from the face of the transducer to t

Page 37 - Programmer Keys

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 117mmmmmParametersAlways prevent the monitored surface from approaching within 0.33m (1 ft) of

Page 38 - Dolphin Plus

Page 118 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersValues4 Half Sphere Bottom5 Flat Sloped Bottom6Flat Ends7 Parabola Ends8 Sphe

Page 39 - Dolphin Plus Toolbar Buttons

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 119mmmmmParametersP051 Maximum Volume For Readings in volumetric units (rather than percent), e

Page 40 - Security

Page 120 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP054 Level Breakpoints (Universal Volume Calculation)When the tank shape is t

Page 41 - Parameters Types

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 121mmmmmParametersEntering a Volume Breakpoint1. Go to Parameter P055.2. For each index enter a

Page 42 - Display Readout

Page 122 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersExamples: • If the measured value is in feet, enter 0.3333 to display the num

Page 43

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 123mmmmmParametersP065 Reading Override ValueThis value is substituted for the current reading

Page 44 - Accessing a Parameter Index

Page 124 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersFailsafe (P070 to P072) P070 Failsafe TimerThe time for invalid measurements

Page 45 - Primary and Secondary Indexes

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 125mmmmmParametersSelecting HI, LO, or HOLd1. Press FUNCTION to display the Auxiliary Functio

Page 47 - Measurement Conditions

Page 126 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersRelays (P100 to P119)The HydroRanger 200 has six relays (or digital outputs)

Page 48 - Relay Function

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 127mmmmmParametersP110 Level SourceSets the level source on which the indexed relay is assigned

Page 49 - 2 % of span

Page 128 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP112 Relay ON SetpointSets the process point at which the relay changes from

Page 50 - Relay Related Parameters

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 129mmmmmParametersP113 Relay OFF SetpointSets the process point at which the relay returns to i

Page 51 - Relay Activation

Page 130 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP118 Relay Output LogicThe logic applied to relays to determine the contact o

Page 52 - Preset Applications

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 131mmmmmParametersP119 Relay Logic TestForces the relay control logic into an ACTIVATED or DE-A

Page 53 - Value # Parameters Affected

Page 132 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP122 Pump Service Ratio Selects pump usage based on the RUN time ratio rather

Page 54

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 133mmmmmParametersTo select an independent Relay Failsafe value:1. Press FUNCTION to display

Page 55 - Discrete Inputs

Page 134 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP131 Pump Run-On Duration Sets the number of seconds that the pump runs on.Yo

Page 56 - Level Reading Parameters

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 135mmmmmParametersP133 Pump Power Resumption Delay Sets the minimum delay before the first pump

Page 57 - Verifying the mA Range

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 1mmmmmHydroRanger 200HydroRanger 200The HydroRanger 200 is a single-point, six relay device tha

Page 58 - Tank Shape and Dimensions

Page 136 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP137 Pump Group Puts pumps into groups for multiple pump rotations on one tra

Page 59 - Characterization Chart

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 137mmmmmParametersP170 Flush Pump Picks the number of the pump relay which triggers the flushin

Page 60

Page 138 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP173 Flush Duration The length of time for each flush cycle that the flush co

Page 61 - Set the Common Parameters

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 139mmmmmParametersP201 mA Output Function Alters the mA output/measurement relationship.P202 mA

Page 62 - Setting Simple Level Alarms

Page 140 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP203 mA Output Value / Transducer Displays current mA output value for the Po

Page 63 - Temperature

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 141mmmmmParametersP210 0/4 mA Output Setpoint Sets the process level corresponding to the 0 or

Page 64 - Loss of Echo (LOE)

Page 142 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP213 mA Output Max Limit Sets the maximum mA output value (in mA) to be produ

Page 65 - Pump Control

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 143mmmmmParametersmA Output Failsafe (P219) P219 mA Output Failsafe Use for failsafe operation,

Page 66 - HydroRanger

Page 144 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP251 0 or 4 mA Input Level Shows the process level corresponding to the 0 or

Page 67

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 145mmmmmParametersP254 Scaled mA Input Value Shows the resulting level value after scaling.This

Page 68 - Other Pump Control Algorithms

Page 2 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmHydroRanger 200Manual SymbolsPlease note their use carefully.Configuration ExamplesThe co

Page 69

Page 146 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP275 Scaled Discrete Input ValueShows the current value of the discrete input

Page 70 - Optional Pump Controls

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 147mmmmmParametersP300 Temperature, Transducer MaximumShows the highest temperature encountered

Page 71 - Single Point Mode

Page 148 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP303 Temperature, Sensor MinimumShows the lowest temperature encountered, as

Page 72 - Totalizing Pumped Volume

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 149mmmmmParametersPump Records (P310 to P312)These features to identify pump usage and if the a

Page 73 - Reducing Wall Cling

Page 150 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP312 Pump Run Ons View or reset the accumulated number of times the displayed

Page 74 - Setting a Flush Valve

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 151mmmmmParametersLCD Totalizer (P322 and P323) Use these features to view, reset, or preset th

Page 75 - Tracking Pump Usage

Page 152 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersProfile Records (P330 to P337) These features can record up to ten Echo profi

Page 76 - Rake (Screen) Control

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 153mmmmmParametersRecording a profile manuallyPress TRANSDUCER to fire the transducer and rec

Page 77 - Set Relay 1 (Operate Rake)

Page 154 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP332 Auto Record TransducerSpecifies the Transducer Point Number for which Au

Page 78 - Totalizer

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 155mmmmmParametersP334 Auto Record ON SetpointEnter the critical level which, in conjunction wi

Page 79 - Flow Sampler

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 3mmmmmSpecificationsSpecificationsPowerAC version• 100-230 Vac ± 15%, 50 / 60 Hz, 36 VA (17W)1•

Page 80 - Common Parameters

Page 156 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP337 Auto Record LOE TimeLimits Auto Profile Records from being saved unless

Page 81 - Setting Zero Head

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 157mmmmmParametersP342 Start UpsThe number of times power has been applied since the Date Of Ma

Page 82 - Setting Totalized Volume

Page 158 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersIf your PMD is not listed, select the appropriate Universal Flow Calculation.

Page 83 - Parameter Index Value

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 159mmmmmParametersExample ExponentsP602 Primary Measuring Device Dimensions The dimensions of t

Page 84 - Palmer Bowlus Flume

Page 160 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP603 Maximum Head The level value associated with Maximum Flow, in Units (P00

Page 85

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 161mmmmmParametersP605 Zero Head The distance above Empty (P006) in Units (P005) representing z

Page 86 - Applicable Weir Profiles

Page 162 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP607 Flowrate Decimal The maximum number of decimal places to be displayed.In

Page 87 - Parshall Flume

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 163mmmmmParametersThis parameter is enabled only if the primary measuring device (PMD) supports

Page 88 - Leopold Lagco Flume

Page 164 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP620 Low Flow Cutoff Eliminates totalizer activity for flows at or below the

Page 89 - Cut Throat Flume

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 165mmmmmParametersPumped Volume Totalizer (P622) The Pumped Volume Totalizer is a HydroRanger 2

Page 90 - Universal Calculation Support

Page 4 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmSpecificationsRange• 0.3m (1 ft) to 15m (50 ft), dependent on transducerAccuracy• 0.25% o

Page 91 - Example Weirs

Page 166 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersTotalizer (P630 to P645) P630 LCD Totalized Multiplier Use this feature if th

Page 92

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 167mmmmmParametersP633 LCD Totalized Decimal Position Enter the maximum number of decimal place

Page 93 - Testing the Configuration

Page 168 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP641 Flow Sampler Mantissa Use this feature in conjunction with Flow Sampler

Page 94

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 169mmmmmParametersP645 Relay Duration Use this feature (if desired) to adjust the minimum conta

Page 95 - Application Test

Page 170 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersBefore using this feature, verify the following parameters are correct:•Empty

Page 96

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 171mmmmmParametersP652 Offset CorrectionThe value altered when an Offset Calibration is perform

Page 97 - Optional SmartLinx

Page 172 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersTemperature Compensation (P660 to P664)P660 Temp SourceSource of the temperat

Page 98 - Communication Ports

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 173mmmmmParametersP663 Temperature Transducer AllocationThis feature may only be used for diffe

Page 99 - SmartLinx

Page 174 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersRate (P700 to P708) These parameters determine how material level changes are

Page 100 - Communications Installation

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 175mmmmmParametersP702 Filling IndicatorThe fill rate required to activate the LCD Filling indi

Page 101 - Port 2: RS-485

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 5mmmmmSpecificationsFixed• 0.17% per °C deviation from programmed valueOutputsTransducer drive•

Page 102 - P771 Network Address

Page 176 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersEnter the time or distance interval over which the Rate Value is to be calcul

Page 103 - P773 Parity

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 177mmmmmParametersP708 Volume Rate Display The rate of change of volume in percent of maximum v

Page 104 - P782 Parameter Index Location

Page 178 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersIf a material agitator (mixer) is used in the vessel monitored, set Echo Lock

Page 105 - Modbus Register Map

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 179mmmmmParametersP713 Echo Lock WindowAdjusts the size of the Echo Lock Window.The Echo Lock W

Page 106 - Map ID (R40,063)

Page 180 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersThis feature may only be used to adjust the delay before the next point is sc

Page 107 - Product ID (R40,064)

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 181mmmmmParametersSelecting the Auxiliary Reading operation1. Press READING to display the Au

Page 108 - Relay Data Address

Page 182 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP733 Scroll AccessUse this feature to select the parameter scroll access opti

Page 109

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 183mmmmmParametersSmartLinx Reserved (750 to 769) These parameters are reserved for optional Sm

Page 110 - Reading Parameters

Page 184 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP772 Baud RateThe communication rate with the master device.This specifies th

Page 111 - Types of values are:

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 185mmmmmParametersP775 Stop BitsThe number of bits between the data bits.P778 Modem AvailableSe

Page 112 - Writing Parameters

© Siemens Milltronics Process Instruments Inc. 2002Safety GuidelinesWarning notices must be observed to ensure personal safety as well as that of oth

Page 113 - Format Registers

Page 6 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmSpecificationsDiscrete (2)• 10-50Vdc switching level• logical 0 = < 0.5 Vdc• logical 1

Page 114

Page 186 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP782 Parameter Index LocationDetermines where index information is stored for

Page 115 - Data Types

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 187mmmmmParametersP791 Bus ErrorIndicates if an error condition is occurring on the bus.P792 Bu

Page 116 - Split Values

Page 188 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP801 Range ExtensionAllows the material level to fall below the Empty setting

Page 117 - Text Messages

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 189mmmmmParametersP803 Shot / Pulse ModeDetermines what type of ultrasonic shots are fired.Use

Page 118 - HydroRanger 200

Page 190 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP805 Echo ConfidenceDisplays the echo confidence of the measurement echo from

Page 119 - Error Handling

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 191mmmmmParametersAdvanced Echo Processing (P810 to P825) The following parameters are for auth

Page 120

Page 192 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersAny combination of the following Scope Displays is available. Two methods to

Page 121 - Communication Troubleshooting

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 193mmmmmParametersP816 Echo Time RawThe time (in ms) from the transmit pulse to the processed e

Page 122 - Parameter Access (SPA)

Page 194 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP818 Profile Pointer DistanceThe distance between the transducer face and the

Page 123 - Format Register

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 195mmmmmParametersUse this to select the algorithm(s) the Sonic Intelligence®echo selection is

Page 124 - Error Codes

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 7mmmmmInstallationInstallationMountingMounting LocationsRecommended• Ambient temperature is alw

Page 125 - Parameter Reference

Page 196 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP823 Reform Echo Smoothes jagged peaks in the echo profile.Use this feature,

Page 126 - Parameters

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 197mmmmmParametersAdvanced TVT Adjustment (P830 to P835) The following parameters are for autho

Page 127 - Quick Start (P001 to P007)

Page 198 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP832 TVT Shaper AdjustAllows manual adjustment of the TVT curve.Use this feat

Page 128 - P003 Maximum Process Speed

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 199mmmmmParametersP833 TVT Start MinUse this feature to adjust the TVT Curve height to ignore f

Page 129 - P005 Units

Page 200 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersAdvanced Shot Adjustment (P840 to P852) These parameters are for Siemens Mill

Page 130 - P007 Span

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 201mmmmmParametersP843 Long Shot FrequencyAdjust the long shot transmit pulse frequency (in kHz

Page 131 - Volume (P050 to P055)

Page 202 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP850 Short Shot BiasUse this feature to slant the echo evaluation in favour o

Page 132

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 203mmmmmParametersTest (P900 to P913)Test Parameters are intended for use by Siemens Milltronic

Page 133 - P053 Tank Dimension L

Page 204 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP904 KeypadPress ENTER , then press each keypad key in the following sequen

Page 134 - Typical volume calculations

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 205mmmmmParametersP910 Toggle RelaysUsed to energize and de-energize relays directly.Enter the

Page 135 - P061 Convert Reading

Page 8 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmInstallationMounting InstructionsMount the unit where there is sufficient room to swing l

Page 136 - Backup Level Override

Page 206 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP913 Sensor TemperatureAccess this parameter to display the temperature in °C

Page 137 - P066 Override Time Delay

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 207mmmmmParametersReading Measurements by OperationP921 Material MeasurementThe distance in Uni

Page 138 - Failsafe (P070 to P072)

Page 208 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersP924 Volume Measurement The calculated vessel capacity in Max Volume (P051) o

Page 139 - P072 Failsafe Level Advance

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 209mmmmmParametersMaster Reset (P999) This feature resets all parameters to original values.Use

Page 140 - Relays (P100 to P119)

Page 210 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmParametersNotes

Page 141 - P111 Relay Control Function

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 211mmmmmAppendix A: Index TypesGeneral Appendix A: Index typesIndex typesName Description # of

Page 142 - P112 Relay ON Setpoint

Page 212 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix B: Tech ReferenceGeneral Appendix B: Technical ReferenceTransmit PulseThe tran

Page 143 - P116 Dead Band

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 213mmmmmAppendix B: Tech ReferenceDolphin Plus DisplayDistance CalculationTo calculate the tran

Page 144 - P118 Relay Output Logic

Page 214 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix B: Tech ReferenceThe HydroRanger 200 automatic temperature compensation is bas

Page 145 - P121 Pump by Rate

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 215mmmmmAppendix B: Tech ReferenceEnter a Level Breakpoint at each point where the level/volume

Page 146 - P129 Relay Failsafe

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 9mmmmmInstallationCable routed through a conduit:1. Remove the four mounting screws holding the

Page 147 - P130 Pump Run-On Interval

Page 216 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix B: Tech ReferenceEnter a Head Breakpoint at each point where the head/flow cur

Page 148 - P132 Pump Start Delay

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 217mmmmmAppendix B: Tech ReferenceMaximum Process SpeedThe HydroRanger 200’s ability to respond

Page 149 - P136 Wall Cling Reduction

Page 218 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix C: TroubleshootingGeneral Appendix C: TroubleshootingIf the setup becomes too

Page 150 - Flush Systems (P170 to P173)

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 219mmmmmAppendix C: TroubleshootingNoise ProblemsIncorrect readings can be the result of noise

Page 151 - P172 Flush Interval

Page 220 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix C: TroubleshootingDetermine the Noise SourceDisconnect the transducer from the

Page 152 - P200 mA Output Range

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 221mmmmmAppendix C: TroubleshootingFiltering cables is an option but is not recommended unless

Page 153 - P202 mA Output Allocation

Page 222 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix C: TroubleshootingMeasurement DifficultiesIf the Failsafe Timer (P070) expires

Page 154 - Settings

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 223mmmmmAppendix C: TroubleshootingDisplaying Echo Confidence in the RUN modePress and hold f

Page 155 - P212 mA Output Min Limit

Page 224 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix C: TroubleshootingIf an obstruction cannot be removed or avoided, adjust the T

Page 156 - P215 20 mA Output Trim

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 225mmmmmAppendix C: TroubleshootingWrong ReadingIf the Reading is erratic, or jumps to some inc

Page 157 - P250 mA Input Range

Page 10 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmInstallationInstalling the BatteryThe battery (Rayovac BR2032) has a ten-year life expec

Page 158 - P252 20 mA Input Level

Page 226 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix C: TroubleshootingNormal Ring DownPoor Ring DownRing down times that extend pa

Page 159 - P270 Discrete Input Function

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 227mmmmmAppendix D: Pump Control General Appendix D: Pump Control ReferenceThe HydroRanger 200

Page 160

Page 228 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix D: Pump Control AlternateStarts pumps based on the duty schedule and always le

Page 161

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 229mmmmmAppendix D: Pump Control Relay TableThe following table shows relay status when each se

Page 162 - P305 Reading Min

Page 230 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix D: Pump Control Alternate Duty Backup (P111 = 53) Alternates the lead pump eac

Page 163 - Pump Records (P310 to P312)

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 231mmmmmAppendix D: Pump Control Service Ratio Duty Assist (P111 = 54) Selects the lead pump ba

Page 164 - Flow Records (P320 and P321)

Page 232 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAppendix D: Pump Control First In First Out (FIFO) (P111 = 56) Selects the lead pump ba

Page 165 - P323 LCD Total High

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 233Appendix E: Updfate SoftwareGeneral Appendix E: Updating SoftwareUpdating SoftwareTo update

Page 166 - P330 Profile Record

Page 234 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmGeneral Appendix FGeneral Appendix F: UpgradingThe following procedure will assist you

Page 167 - P331 Auto Record Enable

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 235mmmmmGeneral Appendix FConnecting a transducer with RG62 coaxial extension cableIf you are r

Page 168 - P333 Auto Record Interval

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 11mmmmmWiringWiringPlease note:• Verify that all system components are installed in accordance

Page 169 - P335 Auto Record OFF Setpoint

Page 236 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmGeneral Appendix FHydroRanger to HydroRanger 200 ParametersThe HydroRanger 200 uses the

Page 170 - P341 RUN Time

7ML1998IFC01 HydroRanger 200 – INSTRUCTION MANUAL Page 237mmmmmIndexIndexAaccuracy 4adding new functions 233alarm 47bounded 49cable fault 49common pa

Page 171 - P342 Start Ups

Page 238 HydroRanger 200 – INSTRUCTION MANUAL 7ML1998IFC01mmmmmIndexcut throat 75H flume 71Leopold Lagco 74Palmer Bowlus 70Parshall 73, 77rectangular

Page 172 - P601 Flow Exponent

7ML1998IFC01 HydroRanger 200 – INSTRUCTION MANUAL Page 239mmmmmIndexoverview 95reading 96writing 98parameter indexing 29, 96parametersadvanced echo p

Page 173 - Example Exponents

Page 240 HydroRanger 200 – INSTRUCTION MANUAL 7ML1998IFC01mmmmmIndexrecording profiles 153register map 91discrete inputs 94input/output 93mA output 94

Page 174 - P604 Maximum Flow

7ML1998IFC01 HydroRanger 200 – INSTRUCTION MANUAL Page 241mmmmmIndexcalculation 214characterization chart 45dimensions 33readings 44tank shape 44univ

Page 175 - P606 Time Units

*7ML19981Fc01*Rev. 1.2

Page 176 - P608 Flowrate Units

Page 12 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmWiringTerminal BoardThe terminal board on the HydroRanger 200 allows all inputs and outp

Page 177 - P611 Breakpoint Flowrates

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 13mmmmmWiringTransducersA 0.1 µF (100V or greater) capacitor is included with the HydroRanger 2

Page 178 - P621 Auto Zero Head

Page 14 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmWiringTemperature SensorAccurate temperature readings are critical to accurate level mea

Page 179

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 15mmmmmWiringLevel System SynchronizationWhen using multiple ultrasonic level monitors, be sure

Page 180 - Totalizer (P630 to P645)

immmmmTable of ContentsTable of ContentsHydroRanger 200 ...

Page 181 - Example:

Page 16 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmWiringDigital CommunicationsWiring the HydroRanger 200 for communications allows it to b

Page 182 - P642 Flow Sampler Exponent

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 17mmmmmOperationOperating the HydroRanger 200The HydroRanger has two modes of operation: RUN an

Page 183 - P650 Offset Calibration

Page 18 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOperationIcons indicating index type (Item 1) edited in PROGRAM mode:Readings in RUN Mod

Page 184

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 19mmmmmOperationStatus ParametersStatus parameters give the operating status of the HydroRanger

Page 185 - P654 Velocity at 20°C

Page 20 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOperationExampleTo reference the displayed level to sea level, enter the distance in Uni

Page 186 - P661 Temp Fixed

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 21mmmmmOperationSetting a Specific Auxiliary ReadingTo display a second auxiliary reading, pres

Page 187 - P664 Temperature

Page 22 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOperationStarting PROGRAM ModeHand ProgrammerThe hand programmer gives you direct access

Page 188 - Rate (P700 to P708)

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 23mmmmmOperationProgrammer KeysKeys Programming Mode Run Mode1 8-digit Totalizer (toggle) 2 Pum

Page 189 - P704 Rate Filter

Page 24 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOperationDolphin PlusUse Dolphin Plus software to configure, monitor, tune, and diagnose

Page 190 - P707 Rate Value

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 25mmmmmOperationDolphin Plus Toolbar ButtonsThe toolbar buttons provide quick access to Dolphin

Page 191 - P711 Echo Lock

iimmmmmTable of ContentsUsing Units or Percent (%) ...

Page 192 - P712 Echo Lock Sampling

Page 26 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOperationActivating the HydroRanger 200All the instructions in the following procedures

Page 193 - P727 Scan Delay

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 27mmmmmOperationWhen P000 is set to 1954, programming is enabled. To disable programming, enter

Page 194 - Display (P730 to P739)

Page 28 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOperationParameter ResetReturning a parameter to factory default.1. Display the appropri

Page 195 - P732 Display Delay

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 29mmmmmOperationChanging Parameters (Dolphin Plus)The other method for changing parameter value

Page 196 - P737 Primary Reading

Page 30 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOperationHydroRanger 200 DisplayThe index number and the index values are displayed abov

Page 197

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 31mmmmmOperationPrimary and Secondary IndexesPrimary Index: relates to direct input or output a

Page 198

Page 32 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOperationExample P054 provides up to 32 breakpoint levels used with P055 (Volume Breakpo

Page 199

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 33mmmmmOperationMeasurement ConditionsThe following information will help you configure your Hy

Page 200 - SmartLinx Hardware Testing

Page 34 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmRelays3RelaysRelays are the primary controls of external devices such as pumps or alarms

Page 201 - P800 Near Blanking

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 35mmmmmRelaysTemperature In high alarm, the function goes on when the temperature rises to the

Page 202 - P801 Range Extension

iiimmmmmTable of ContentsOther Pump Control Algorithms ...

Page 203 - P804 Confidence Threshold

Page 36 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmRelaysRelay Status – Non Run Modes When the fail-safe timer expires, pump control relays

Page 204 - P807 Noise

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 37mmmmmRelaysP111–Control FunctionsThe control function energizes the relay coils. When the ins

Page 205 - P810 Scope Displays

Page 38 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmRelaysFunctions affected by setpoint are configured by parameters that determine the app

Page 206 - P815 Echo Time Filtered

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 39mmmmmRelaysReservoir 13Pump up with the following level settings:ParameterRelay #123456P111 5

Page 207 - P817 Profile Pointer Time

Page 40 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmBackup Level OverrideBackup Level OverrideBackup level override provides the option of o

Page 208 - P820 Algorithm

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 41mmmmmDiscrete InputsDiscrete InputsWiring the Discrete InputsNormal state is standard operati

Page 209 - P822 Narrow Echo Filter

Page 42 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmmA I/OmA I/OTo integrate the HydroRanger 200 with other equipment, use the mA input and

Page 210 - P825 Echo Marker Trigger

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 43mmmmmmA I/OCalibrating 4 mA Output1. Connect the mA receiving device to the HydroRanger 200.

Page 211 - P831 TVT Shaper

Page 44 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmVolumeVolume Volume is used in two situations:1. Calculate and display volume instead of

Page 212 - P832 TVT Shaper Adjust

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 45mmmmmVolumeCharacterization Chart If you cannot use a pre-defined tank, then use one of the u

Page 213 - P835 TVT Slope Min

ivmmmmmTable of ContentsSimulating a Level Cycle ...

Page 214 - P842 Short Shot Frequency

Page 46 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmVolumeParameter Transducer Index Value DescriptionP054 110.0Determines the Level breakp

Page 215 - P845 Long Shot Width

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 47mmmmmAlarmsAlarmsLevelThe level alarm is the most common. Use this alarm to warn you when you

Page 216 - P852 Short Shot Range

Page 48 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAlarmsSetting Simple Level AlarmsTo set Relay Five to a standard level alarm (Hi Hi, Hi,

Page 217 - Test (P900 to P913)

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 49mmmmmAlarmsIn Bounds / Out of Bounds Range Use the bounded range alarms to detect when the le

Page 218 - P908 Scanner

Page 50 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmAlarmsWith P112 and P113, you can set a high alarm (P112 > P113) or a low alarm (P112

Page 219 - P912 Transducer Temperature

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 51mmmmmPump ControlPump ControlSetting a Pump Down GroupExample: Sewage Wet WellSetting a group

Page 220 - Measurement (P920 to P927)

Page 52 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmPump ControlSet Relays to ALTERNATE DUTY ASSIST Set the ON SetpointsSet the OFF Setpoint

Page 221 - P923 Distance Measurement

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 53mmmmmPump ControlSet the Common Parameters Prerequisite: Substitute the details of your appli

Page 222 - P927 Distance Measurement

Page 54 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmPump ControlOther Pump Control AlgorithmsSet Relays to ALTERNATE DUTY BACKUP Set the Rel

Page 223 - Master Reset (P999)

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 55mmmmmPump ControlSet Relays to FIXED DUTY BACKUP Set the Relay ON Setpoints Set the Relay OFF

Page 224

vmmmmmTable of ContentsBit Values ...

Page 225 - Index types

Page 56 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmPump ControlSet Relays to FIRST IN FIRST OUT (FIFO) ASSIST Set the Relay ON Setpoints Se

Page 226 - Echo Processing

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 57mmmmmPump ControlWhen the first ON setpoint is reached, the pumps will start, one by one, unt

Page 227 - Sound Velocity

Page 58 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmPump ControlTotalizing Pumped Volume Prerequisite: the volume of the vessel must be know

Page 228 - Volume Calculation

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 59mmmmmPump ControlSetting a Pump to Run On When you need to pump below the normal OFF setpoint

Page 229 - Flow Calculation

Page 60 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmPump ControlExample :A range of 0.5 meters is used to vary the setpoint. The randomly-se

Page 230 - Universal, Curved

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 61mmmmmPump ControlExample: The flush valve connects to Relay Four and the watched pump is on R

Page 231 - Maximum Process Speed

Page 62 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01Rake (Screen) Control Rake (Screen) Control Screens or rakes are mounted on the inflow channe

Page 232 - Common Problems Chart

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 63mmmmmRake (Screen) ControlSetting the Common ParametersPrerequisite: Substitute the details o

Page 233 - Noise Problems

Page 64 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmExternal Totalizers and Flow Samplers External Totalizers and Flow Samplers External tot

Page 234 - Non-Transducer Noise Sources

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 65mmmmmExternal Totalizers and Flow Samplers The source of units depends on the operation:Flow

Page 235 - Reducing Acoustical Noise

vimmmmmTable of ContentsRelays (P100 to P119) ...

Page 236 - Measurement Difficulties

Page 66 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOpen Channel MonitoringOpen Channel Monitoring (OCM) An OCM installation is defined one

Page 237 - Fixed Reading

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 67mmmmmOpen Channel MonitoringSetting Zero HeadMany PMDs start flowing higher than the traditio

Page 238 - Nozzle Mountings

Page 68 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOpen Channel MonitoringSetting Totalized VolumeTo display the totalized volume on the LC

Page 239 - Transducer Ringing

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 69mmmmmOpen Channel MonitoringBS-3680 / ISO 4359 Rectangular FlumeParameter Index ValueP600 G 6

Page 240 - Poor Ring Down

Page 70 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOpen Channel MonitoringPalmer Bowlus FlumeApplication Information• Sized by pipe diamete

Page 241 - Reference

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 71mmmmmOpen Channel MonitoringH Flume• Sized by maximum depth of flume• Approach is preferably

Page 242 - Off 0 Off Off Off

Page 72 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOpen Channel MonitoringPMDs with Exponential Flow to Head FunctionFor Primary Measuring

Page 243

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 73mmmmmOpen Channel MonitoringNon-Applicable Weir ProfilesFlows through these weirs can be meas

Page 244

Page 74 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOpen Channel MonitoringLeopold Lagco FlumeApplication Information• Designed to be instal

Page 245 - P122 Index Value

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 75mmmmmOpen Channel MonitoringCut Throat FlumeApplication Information• Similar to Parshall flum

Page 246 - Other Pump Controls

viimmmmmTable of ContentsP270 Discrete Input Function...

Page 247 - Updating Software

Page 76 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOpen Channel MonitoringUniversal Calculation SupportWhen the primary measuring device (P

Page 248 - General Appendix F: Upgrading

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 77mmmmmOpen Channel MonitoringExample FlumesThese example flumes would both require a universal

Page 249 - Existing installation

Page 78 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmOpen Channel MonitoringNotes

Page 250 - Relay Parameter Value

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 79mmmmmTesting the ConfigurationTesting the ConfigurationAfter programming the unit, you must t

Page 251

Page 80 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmTesting the ConfigurationThe effect of the ARROW key is determined by the state (rate of

Page 252

7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 81mmmmmTesting the ConfigurationI/O CheckoutAfter you have installed the unit, we recommend tha

Page 253

Page 82 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01mmmmmTesting the ConfigurationMonitor system performance carefully, under all anticipated ope

Page 254

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 83mmmmmCommunicationsHydroRanger 200 CommunicationsHydroRanger 200 Communication SystemsThe Hyd

Page 255

Page 84 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1mmmmmCommunicationsCommunication SystemsThe HydroRanger 200 is capable of communicating with

Page 256 - *7ML19981Fc01*

7ML19981FCO1 HydroRanger 200 – INSTRUCTION MANUAL Page 85mmmmmCommunicationsSmartLinxOther protocols are available through optional SmartLinx communic