Commissioning (software)
2.7 Commissioning modes
Control Units CU240S
Operating Instructions (Compact), 04/2006, A5E00766042B AA
2-51
Successful automatic download
After a successful automatic download, F0395 will be displayed.
In case of a standard CU a confirmation is necessary.
In the case of CUs with safety integrated functions, an acceptance test must be
performed.
Confirmation
On standard CUs the current parameter set needs to be checked and confirmed by clearing
F0395. It can be cleared via:
Digital input or PLC signal (depends on the settings of P0700)
setting P7844 = 0.
Warning
The user is responsible for ensuring that the parameters held in the CU are the correct
parameters for their application.
Acceptance test
On CUs with integrated fail-safe functions it is necessary to do an acceptance test (refer to
the "Safety-Integrated functions" section in this manual). To clear F0395 on CUs with
integrated fail-safe functions the following procedure has to be followed:
P0010 = 95
P9761 = fail-safe password
P7844 = 0
Automatic download fault
If the automatic download process fails, the CU will return to the parameter set previously
held in the EEPROM and the following fault codes are generated:
Table 2-17 Automatic download fault codes
Fault code Description
F0061 Automatic download of parameters was not successful.
F0063 Automatic download of parameters was not successful (e.g. wrong CU).
In this case check, wether the MMC is defective or a parameter set clone00.bin is available
or the parameter set is valid.