Commissioning (software)
2.4 Parameterization with Operator Panel
Control Units CU240S
2-12 Operating Instructions (Compact), 04/2006, A5E00766042B AA
2.4.2 Function Keys of the OP
Operator Panel - function keys
Table 2-12 OP keys and their functions
Operator Panel
Key
Function Effects
Status
display
The LCD indicates the settings which the drive inverter is presently using.
Start motor The inverter is started by pressing the key. This key is deactivated in the default setting.
Parameter P0700 or P0719 should be changed as follows to activate the key:
OP: P0700 = 1 or P0719 = 0 ... 16
OFF1 When this key is pressed, the motor comes to a standstill within the selected
ramp-down time. It is deactivated in the default setting; to activate → refer to the
"Start motor" key.
Stop motor
OFF2 The motor coasts down to a standstill by pressing the key twice (or pressing
once for a longer period of time). This function is always activated.
Direction
reversal
To reverse the direction of rotation of the motor, press this key. The opposing direction is
displayed using the minus character (-) or by the flashing decimal point. In the default
setting this function is deactivated. To activate it → refer to the "Start motor" key.
Jog motor In the "Ready to power-on" state, when this key is pressed, the motor starts and rotates
with the pre-set jog frequency. The motor stops when the key is released. When the motor
is rotating, this key has no effect.
Function This key can be used to display additional information.
If you press the key during operation, independent of the particular parameter, for two
seconds, the following data will be displayed:
1. Voltage of the DC current link (designated by d – units V).
2. Output current (A)
3. Output frequency (Hz)
4. Output voltage (designated by o – units V).
5. The value, selected in P0005 (if P0005 is configured so that one of the above pieces
of data is displayed (1 to 4), then the associated value is not re-displayed).
The displays mentioned above are run-through one after the other by pressing again.
Step function
Starting from any parameter (rXXXX or PXXXX), if the key Fn is briefly pressed, then a
jump is immediately made to r0000. You can then, when required, change an additional
parameter. After returning to r0000, when key Fn is pressed, then the system returns to
the starting point.
Acknowledgement
If alarm and fault messages are present, then these can be acknowledged by pressing
key Fn.
Parameter
access
Parameters can be accessed by pressing this key.
Increase
value
When this key is pressed, the displayed value is increased.
Reduce
value
When this key is pressed, the displayed value is decreased.