Siemens CU240S DP Operations Instructions Page 52

  • Download
  • Add to my manuals
  • Print
  • Page
    / 110
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 51
Commissioning (software)
2.7 Commissioning modes
Control Units CU240S
2-32 Operating Instructions (Compact), 04/2006, A5E00766042B AA
2.7.8.4 Flow chart - Temperature Sensor
Temperature Sensor
Parameter Description (Factory setting: bold) Setting
P0601 = 0
or
P0601 = ?
Motor temperature sensor
0: No sensor (→ P0610)
1: PTC thermistor (→ P0604)
2: KTY84 (→ P0604)
P0604 = ? Threshold motor temperature
Enter the warning threshold for motor overtemperature protection. The trip temperature
(threshold) is where either the inverter is tripped or Imax is reduced (P0610) which is always
10 % above the warning threshold.
P0610 = 2 Motor I2t temperature reaction
Defines the reaction when the mtor temperature reaches the warning threshold.
0: No reaction, only a warning
1: Warning and I
max
reduced (this results in a reduced output frequency)
2: Warning and trip (F0011)
Temperature calculation without sensor
In the vector control mode (P1300 = 20/21/22/23) Temperature calculations is possible
without sensor. The following parameters have to be set.
Parameter Description (Factory setting: bold) Setting
P0621= 1 Motor temperature identification after restart
0: No identification
1: Temperature identification only at first "motor on" after power cycle
2: Temperature identification at each motor on.
P0622 = Motor magnetizing time for temperature identification after stator restistance identification
This parameter will be initialised with a value for one calculating cycle of the motor
temperature. It depends on the identified rotor time constant. Due to accuracy reasons this
calculation may be performed several times.
2.7.8.5 Flow chart - Command source
Selection of command source
The available command sources depend on the used CU.
Default setting on the control unit used the command source is set per default to different
values.
Page view 51
1 ... 51 52 53 ... 110

Comments to this Manuals

No comments