Commissioning (software)
2.7 Commissioning modes
Control Units CU240S
2-50 Operating Instructions (Compact), 04/2006, A5E00766042B AA
adjust CU parameters
according to
Power Stack data
wait for
acceptance test /
confirmation
F0395
Power Stack type
compliant?
Ready
P7844 = 1?
(acceptance test/
confirmation)
P8458 = 1?
(Clone Control)
P8458 = 0
(Clone Control)
valid Par.
set?/Safety settings
compliant?
P8458 > 0?
(Clone Control)
MMC plugged?
yes
go to
Swap behavior
QR
swap?
Power ON
yes
QR
QR
yes
yes
QR
yes
QR
yes
QR
QR
yes
MMC fault
F0061/F0063
Figure 2-12 Automatic download - overview
The possible settings for P8458 and their functions are given below.
P8458 = 0: Automatic parameter download from the MMC is inhibited.
P8458 = 1: Automatic parameter download from the MMC only at the first start-up of the
CU (default setting).
P8458 = 2: Automatic parameter download from the MMC after each start-up of the
control unit.