Commissioning (software)
2.7 Commissioning modes
Control Units CU240S
Operating Instructions (Compact), 04/2006, A5E00766042B AA
2-21
Parameter Action/Description (Factory setting: bold)
Parameters with an "*" have more settings than listed below. Please refer to the parameter list
Your own
setting
2: 4-pole motor
Recalculated automatically when P0310 (rated motor frequency) or P0311 (rated motor speed)
is changed.
P0320 = ? Motor magnetizing current
Setting P0320 = 0 causes calculation according the setting of P0340 = 1 (data entered from
rating plate) or by P3900 = 1, 2 or 3.
The calculated value is displayed in parameter r0331.
P0335 = 0 Motor cooling
0: Self-cooled using shaft mounted fan attached to the motor
1: Force-cooled, using a separately powered cooling fan
2: Self-cooled and internal fan
3: Force-cooled and internal fan
P0400 = 0 Select encoder type
0: Disabled
2: Quadrature encoder no zero pulse
12: Quadrature encoder & zero pulse
Note: Encoders with zero pulse can also be connected, but the zero pulse is not used.
P0408 = ? Encoder pulses per revolution
Specifies the number of encoder pulses per revolution (encoder resolution)
Note: The encoder resolution is limited by the max. pulse frequency of the encoder circuits
(f_max = 300 kHz).
P0500 = 0 Technological application
Selects technological application
0: High overload
1: Light overload (for pumps and fans, etc. sets internally P1300 = 2)
P0610 = 2 Motor I2t temperature reaction
Defines reaction when motor temperature reaches warning threshold.
0: No reaction, warning only
1: Warning and Imax reduction
2: Warning and trip (F0011)
P0625 = ? Ambient motor temperature
Ambient temperature of motor at time of motor data identification.
Note: It is only allowed to change the value when the motor is cold. A motor identification has
to be made after changing the value.
P0640=150 Motor overload factor
Defines motor overload current limit [%] relative to P0305 (rated motor current).
This defines the limit of the maximum output current as a percentage of the rated motor
current (P0305). This parameter is set, using P0205 for high overload, to 150 % and for light
overload, up to 110 %.
P0700 = 2 Selection of command source*
enter the command source
0: Factory default setting
1: OP (keypad)
2: Terminal (Default for CUS240S)
4: USS on RS232
5: USS on RS485
6: Fieldbus (Default for CUS240S DP and CUS240S DP-F)
P0727 = 0 Selection of 2-/3-wire method
Determines the control method using the terminals.
0: Siemens (start/dir)
1: 2-wire(fwd/rev)
2: 3-wire(fwd/rev)