Commissioning (software)
2.7 Commissioning modes
Control Units CU240S
Operating Instructions (Compact), 04/2006, A5E00766042B AA
2-35
Frequency setpoint via MOP (P1000 = 1)
Parameter Description (Factory setting: bold) Setting
P1031 = 0 Setpoint memory of the MOP
The last motorized potentiomenter setpoint, which was active before the OFF command or
switching-off, can be saved.
0: MOP setpoint will not be stored
1: MOP setpoint will be stored in P1040
P1032 = 1 Inhibit reverse direction of MOP
0: reverse direction is allowed
1: Reverse direction inhibited
P1040 = 5 Setpoint of the MOP
Defines the setpoint [Hz] of the motorized potentiometer (MOP).
Frequency setpoint via analog input (AI) (P1000 = 2)
Parameter Description (Factory setting: bold) Setting
P0756 = 0 AI type
Defines the type of the analog input and also enables analog input monitoring.
0: Unipolar voltage input (0 to +10 V)
1: Unipolar voltage input with monitoring (0 V … +10 V)
2: Unipolar current input (0 mA … 20 mA)
3: Unipolar current input with monitoring (0 mA … 20 mA)
4: Bipolar voltage input (-10 V … +10 V)
NOTE: The following applies for P0756 … P0760:
Index 0: Analog input 0 (AI0), terminals 3 and 4
Index 1: Analog input 1 (AI1), terminals 10 and 11
P0757 = 0 Value x1 of AI scaling [V/mA]
P0758 = 0.0 Value y1 of AI scaling
this parameter represents the value of x1 as a
percentage of P2000 (reference frequency)
P0759 = 10 Value x2 of AI scaling [V/mA]
P0760 = 100 Value y2 of AI scaling
This parameter represents the value of x2 as
a percentage of P2000 (reference frequency)
$63PD[

9
P$
9
P$
[

3
3
3
3!
33
__
!3!3
$63PLQ
3
3
3 3
K