Troubleshooting/FAQs
Control Units CU240S
5-6 Operating Instructions (Compact), 04/2006, A5E00766042B AA
Troubleshooting with the OP
If the motor fails to start when the ON command has been given:
• Check that P0010 = 0.
• Check the inverter state via r0052
• Check command and setpoint source (P0700 and P1000)
Warnings and faults are displayed on the OP with Axxx and Fxxx respectively. The individual
messages are shown in the Parameter List.
Note
Motor data must relate to the inverter data power range and voltage.