Commissioning (software)
2.7 Commissioning modes
Control Units CU240S
2-44 Operating Instructions (Compact), 04/2006, A5E00766042B AA
To copy a parameter set from one inverter to another, the following procedure should be
performed.
Upload a parameter set with an OP
Prerequisites
An inverter with an apropriate parameter set is available (upload inverter)
Supply voltage is active for the upload inverter
The upload inverter is in "Ready State".
Parameter Action / Description (Factory setting: bold) Setting
Fit the OP to the Inverter - for the parameter set to be uploaded, perform the following steps:
P0003 = 3 User access level*
1: Standard: Allows access into most frequently used parameters
2: Extended: Allows extended access e.g. to inverter I/O functions
3: Expert: For expert use only
P0010 = 30 Commissioning parameter*
0: Ready
1: Quick commissioning
2: Inverter
30: Factory setting, parameter transfer
95: Commissioning the fail-safe functions (CUs with Safety-Integrated functions only)
P0802 = 1 Transfer data from EEPROM
0: Disabled
1: Start OP transfer
2: Start MMC Transfer
While the upload is active "bUSY" will be displayed on the OP and the inverter will not react to
any commands.
If the upload has been completed successfully, P0010 and P0802 will be set to 0 and the OP
display will return to normal.
If the upload has failed, F00055 (failure while saving parameter on OP) or F00057 (OP fault)
will be displayed.
In this case attempt another download or perform a factory reset.
After a successful upload disconnect the OP from the upload inverter.
Download a parameter set with an OP
Prerequisites
Supply voltage is active for the download inverter
The download inverter is in "Ready State".
Parameter Action / Description (Factory setting: bold) Setting
Fit the OP to the inverter and perform the download according the flow chart.
P0003 = 3 User access level*
1: Standard: Allows access to the most frequently used parameters
2: Extended: Allows extended access e.g. to inverter I/O functions