Commissioning (software)
2.7 Commissioning modes
Control Units CU240S
2-38 Operating Instructions (Compact), 04/2006, A5E00766042B AA
2.7.8.9 Flow chart - JOG frequency
JOG frequency
Parameter Description (Factory setting: bold) Setting
P1057 = 1 JOG Enable
P1057 = 0 JOG-function diabled
P1057 = 1 JOG-function enabled
P1058 = 5 JOG frequency right
Frequency in Hz when the motor is being jogged in the clockwise direction of roatation.
P1059 = 5 JOG frequency left
Frequency in Hz when the motor is being jogged in the counter-clockwise direction of rotation.
P1060 = 45 JOG ramp-up time
Ramp-up time in seconds from 0 to the
maximum frequency (P1082). The JOG ramp-up
is limited by P1058 or P1059.
P1061 = 50 JOG ramp-down time
Ramp-down time in seconds from the maximum
frequency (P1082) to 0.
3
3
W
3 3
I
I
PD[
2.7.8.10 Flow chart - Additional Setpoints
Additional Setpoints
Parameter Description (Factory setting: bold) Setting
P1074 = 1.0 BI: disable additional setpoint
P1075 = 775 CI: additional setpoint
Defines the source of the additional setpoint which is added to the main setpoint.
Common settings:
755: Analog input setpoint
1024: Fixed frequency setpoint
1050: MOP setpoint
P1076 = 1.0 CI: additional setpoint scaling
Defines the source to scale the additional setpoint.
Common settings:
1: Scaling of 1.0 (100 %)
755: Analog input setpoint
1024: Fixed frequency setpoint
1050: MOP setpoint