Commissioning (software)
2.3 Factory settings
Control Units CU240S
2-10 Operating Instructions (Compact), 04/2006, A5E00766042B AA
Table 2-11 Pre-assignment of the digital inputs for a CU240S *)
Digital Inputs Terminals Parameter Function Active
Command source* - P0700 = 2 Terminals Yes
Digital Input 0, DI0 5 P0701 = 1 ON/OFF1 Yes
Digital Input 1, DI1 6 P0702 = 12 Reversing Yes
Digital Input 2, DI2 7 P0703 = 9 Fault acknowledge Yes
Digital Input 3, DI3 8 P0704 = 15 Fixed setpoint (direct) No
Digital Input 4, DI4 16 P0705 = 16 Fixed setpoint (direct) No
Digital Input 5, DI5 17 P0706 = 17 Fixed setpoint (direct) No
Digital Input 6, DI6 40 P0707 = 18 Fixed setpoint (direct) No
Digital Input 7, DI7 41 P0708 = 0 Digital input disabled No
Digital Input 8, DI8 42 P0709 = 0 Digital input disabled No
*) With CU240S DP and CU240S DP-F control units, P0700 and P1000 are set to 6 (command
source and setpoint source via PROFIBUS-DP).
If all the installation and commissioning requirements are met and the motor data matches
the inverter data, the following is possible with the factory settings, when using a control unit
CU240S:
To start and stop the motor Using DI0 with external switch
To reverse direction of rotation Using DI1 with external switch
To reset faults Using DI2 with external switch
To enter a frequency setpoint Using AI0 with external potentiometer;
the default setting of the AI: Voltage input
To display the actual frequency value Using AO0 as current output
The potentiometer and the external switches can be connected through the inverter internal
power supply, as shown in section "Connecting the Control Unit via terminals".
Notice
If settings have to be made which go beyond the factory settings, then depending on the
complexity of the application, when commissioning the inverter, the particular function
description as well as the parameter list including function charts must be carefully taken into
consideration.