Commissioning (software)
2.7 Commissioning modes
Control Units CU240S
2-46 Operating Instructions (Compact), 04/2006, A5E00766042B AA
Download a parameter set with STARTER
Prerequisites
Supply voltage is active for the download inverter
The download inverter is in "Ready State".
Connect the STARTER PC via the Option Port (USS on RS232, peer to peer) to the
download inverter (PC connection Kit requiered), press the online button
and perform the
download by activating the button
. The data set must be saved in the EEPROM.
Note
If you want to perform an manual download of a parameter set with STARTER from an
MMC, P0010, P0803 and P0804 must be set via the expert list.
2.7.9.4 Inserting and removing the MMC
Inserting the MMC
To insert an MMC into the Control Unit of the inverter, the process shown in the figure below
should be performed.
6,1$0,&6
6,1$0,&6
Figure 2-10 Installing the MultiMedia Card (MMC)