Commissioning and diagnostics
SIMATIC - ET 200pro motor starters
GWA 4NEB 950 5661-02 DS 06
4-17
Device diagnostics
In the input process image for the starters, the current group fault (DI 0.2)
and group warning messages (DI 0.3) are sent cyclically where necessary.
More in-depth information on the fault type are accessible where necessary
via a diagnostics call (V1-system diagnostics).
All device-specific diagnostics are summarized in the data record 92 (29 bytes).
The content of DS 92 can be exported using ’ES Motor Starter via the device
interface or online via DP V1 using the ’Read data record’ function.
4.6 Software ’ES Motor Starter’
Features
The ’ES Motor Starter’ software (from version 2006) offers you:
• Structured and tool-supported configuration of low-voltage switching devices
• Quick diagnostics
Local commissioning and monitoring on site such as:
• Parameter assignment during operation of the programmable controller and
control system
• Observation
• Diagnostics and testing
•Factory setting
• Read individual phase currents as direct values
• Residual current detection
• A parameterization block can be set
• Integrated online help
• Read statistics and measured values