Siemens HF 35M 562 B Specifications Page 227

  • Download
  • Add to my manuals
  • Print
  • Page
    / 262
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 226
Data formats and data records
SIMATIC - ET 200pro motor starters
GWA 4NEB 950 5661-02 DS 06
D-9
D.5.2 DS73 – Log book – Read trips
This data record can take up to 21 inputs. When all positions have been written
to, the oldest entry is overwritten.
Note
The most recent entry is entered at the end of the data record. The remaining
entries are moved upwards one entry.
The following device faults can be entered:
Byte Meaning Value range Increment Note
0…3 Operating hours device 1…4294967295 1 s
oldest entry
4…5 Object number 0…32767 1
120…123 Operating hours device 1…4294967295 1 s
last, latest
entry
124…125 Object number 0…32767 1
Table D-8: DS73 – Log book – Read trips
Object
no.
Trips - Messages Note
309 Overload switching element only with soft starters
317 Electronics power supply too low
318 Switching element power supply missing
319 No supply voltage only with soft starters
324 Temperature sensor overload
325 Temperature sensor wire break
326 Temperature sensor short-circuit
327 Thermal motor model overload
334 I
e
limit value exceeded
335 I
e
limit value not reached
338 Zero current shutdown
339 Motor blocking shutdown
341 Asymmetry shutdown
348 Input tripping
Table D-9: Messages in the log book – Trips