Device functions
SIMATIC - ET 200pro motor starters
10-16 GWA 4NEB 950 5661-02 DS 06
Response on overload - temperature sensor
This parameter is used to determine how the motor starter responds to a tem-
perature sensor overload and if the temperature sensor monitoring is actuated:
Shutdown without restart
Shutdown with restart
Warning
Caution
Restart means that with a switch-on command present, the motor starter
will automatically be re-started when the cause of the fault has been rectified
(autoreset).
Temperature sensor monitoring
This device parameter is used to determine whether the temperature sensor
line is monitored for interruption and short-circuit.
Range: Yes / no
Temperature sensor parameter – settings
The table below shows the device parameter settings:
Device parameters Default setting Adjustment range
Temperature sensor Deactivated Deactivated / Thermo-
click / PTC - type A
Response on overload -
temperature sensor
Shutdown without
restart
Shutdown without
restart / shutdown
with restart / warning
Temperature sensor monitoring yes Yes / no
Table 10-8: Temperature sensor parameter – settings