Siemens HF 35M 562 B Specifications Page 162

  • Download
  • Add to my manuals
  • Print
  • Page
    / 262
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 161
Device functions
SIMATIC - ET 200pro motor starters
10-24 GWA 4NEB 950 5661-02 DS 06
Quick stop
Motor and brake output are switched off without a group fault.
"Quick stop" has priority over "Motor cw" and "Motor ccw"
The input action responds to the active edge of the input signal.
Deactivation with static "Quick stop" input signal present is therefore
possible.
The input trigger is cleared by removing the "Motor cw" and "Motor ccw"
control commands or via "Lock quick stop" (in the process image).
Example 1:
Digital input 1–signal = retentive / edge-triggered
Motor is switched on by "Motor cw".
Motor is switched on via "Motor cw", then switched off via the rising edge on digital input 1
(parameterized on input action1 = quick stop). Removing the "Motor cw" command resets
the quick stop function.
Motor is switched on via "Motor cw", then switched off via the rising edge on digital input 1.
Setting lock quick stop resets the quick stop function and the motor runs "cw" again until
the "motor cw" command is cancelled.
Motor is switched on via "Motor cw", then switched off via the rising edge on digital input 1.
Setting lock quick stop resets the quick stop function and the motor runs "cw" again.
Although digit input 1 (DI2) is still static, the motor continues to run and is only reset after
cancelling the "motor cw" command.
Reason: The input action is edge-triggered.
Motor is switched on via "Motor cw" and continues to run uninterrupted as lock quick stop
overwrites the edges of the signals of digital input 1 (DI2).
Motor cw signal
Digital input 1
Function Quick stop
Lock Quick stop signal
Motor
①②