Page view 50
Installation
SIMATIC - ET 200pro motor starters
GWA 4NEB 950 5661-02 DS 06
3-7
3.5 Installation of special modules and motor starters
Requirements
All rear wall bus modules for electronics modules, special modules and motor
starters are installed.
Installation of special modules and motor starters
The special modules and motor starters are inserted onto the installed rear wall
bus modules and screwed onto the module carrier using 3 Phillips bolts.
The Phillips bolts are pre-fitted onto the special modules and motor starters
to avoid loss. A maximum of 3 ASM modules are permitted to be driven by
one F-RSM module.
Caution
Ensure that the seal is securely seated and observe the tightening torque of
the Phillips bolts of 1.5 Nm to ensure that the construction is fully sealed.
The table below uses an example of installing a repair switch module.
Drawing Procedure / description
1
2
Set the repair switch with
the trunnion into both retainers
on the rear wall bus module.
Use a size 2 screwdriver to screw
the repair switch module using
the 3 Phillips bolts with a tighten-
ing torque of 1.5 Nm.
Table 3-3: Repair switch module installation