Device functions
SIMATIC - ET 200pro motor starters
GWA 4NEB 950 5661-02 DS 06
10-21
Input n level
This parameter can be used to specify the input logic.
Range: NO contact / NC contact
Caution
With ’n input – action: ’Emergency start’, ’Motor cw’, ’Motor ccw’ and
’Trip reset’, ’n input – level’ can only be parameterized as a NO contact!
Caution
If ’n input – level’ of normally closed and normally open contacts and the associ-
ated ’n input – action are parameterized to Shutdown without restart’, with an
open input the shutdown input’ signaling bit is and shut down accordingly due
to the input signal delay!
Caution
The input level of the digital inputs is always sent to the control (PLC) as a NO
contact, regardless of parameter ’n input – level’ (process image of the inputs
in data record 69 and diagnostics in data record 92).
Input n action
A variety of actions can be triggered by an input signal. The following actions
can be parameterized, depending on ’n input – level’, ’n input – signal’ and
’Operating mode.
Caution
When ’n input signal’ = retentive and n input action = motor cw / ccw, at
least one input with input action ’Shutdown …’ or ’Quick stop’ always needs
to be parameterized.
If this rule is violated, the parameters are rejected with the relevant diagnostics
message!